Brand: Tripp-Lite
|
SKU:
523966
Tripp-Lite PDUMH20HVATNET | 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA
Regular price
$1,505.10
Unit price
-
Low prices.
Price match guarantee
-
In-House Experts.
We know our products
-
Easy Returns.
Quick & Hassle Free
-
Superior Selection.
Extensive product catalog
Brand: Tripp-Lite
|
SKU:
523966
Regular price
$1,505.10
Unit price
Description
Description
Tripp-Lite PDUMH20HVATNET | 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA
Features
- 200-240V 20A Automatic Transfer Switch (ATS) / Switched PDU (Agency de-rated to 16A continuous)
- Enables redundant A/B power option for single-corded network devices
- 2 digit display reports power consumption in amps
- 1U horizontal rackmount form factor
- 10 outlets (8 C13 switched / 2 C19 unswitched)
- Set of Plug-lock output power cable retention sleeves prevent accidental disconnection of connected devices
- Two C20 inlets for separate Primary and Secondary inputs; two 12 ft / 3.7m C20 input cables included
- ATS circuits normally maintain output sourced from the primary input cable; As primary input power fails, the ATS will switch to maintain output sourced from the secondary input cable until power on the primary input is restored and stable
- ATS configurations enable hot-swappable UPS protection when used with a single UPS and redundant UPS protection when each cord is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time)
- Advanced ATS configurations utilizing separate mains circuits, backup generators and separate out of phase utility power grid feeds are supported
- On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower quality than the primary source
- 2-7 millisecond transfer time
- Switched outlets and ethernet interface supports individual outlet control on a real-time or programmable basis and user-specified alarm notification thresholds for all reported site power conditions
- LX Platform interface allows full remote access for power monitoring with email notifications via secure web browser, SNMP, telnet or SSH
- Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities
- Outlets are factory programmed for sequential turn-on at 250 millisecond intervals when the PDU is first energized
- LEDs confirm power availability on both input lines and for each output receptacle
- Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases
Special Features
| High Availability PDU Features | Auto Probe Monitoring and Reboot (included) |
|---|
Specifications
Specifications
Highlights
- Single phase 16A 200-240V Auto Transfer Switch / ATS PDU
- Enables redundant A/B power option for non-redundant network devices
- Built-in LX Platform Network Interface
- 1U horizontal rackmount; 10 outlets (8 C13 switched / 2 C19 unswitched)
- Individually switched outlets, network interface and 2 digit visual current meter
- TAA Compliant
Package Includes
- Switch, Metered PDU with ATS Support
- Set of 2 C19 to C20 12 ft. / 3.7m power cables
- Plug-lock cable retention sleeves
- User manual with warranty information
Overview
| UPC Code | 37332151506.0 |
|---|---|
| PDU Type | Auto-Transfer Switch; Switched |
Input
| PDU Input Voltage | 200-240V DUAL INPUT |
|---|---|
| Recommended Electrical Service | Two single-phase 16/20A 200-240V circuits |
| Maximum Input Amps | 16 |
| Maximum Input Amps Details | Agency de-rated to 16A continuous |
| PDU Plug Type | (2) IEC-320 C20 |
| Input Phase | Single-Phase |
Output
| Output Capacity Details | 3.84kW (240V), 3.68kW (230V), 3.52kW (220V), 3.33kW (208V), 3.2kW (200V) / 16A total capacity; 16A max per C19 outlet; 12A (10A CE) max per C13 outlet |
|---|---|
| Frequency Compatibility | 50 / 60 Hz |
| Output Receptacles | (8) C13; (2) C19 |
| Output Nominal Voltage | 200-240V |
| Overload Protection | - |
| Customized Load Management Receptacles | 8 individually switched C13 output receptacles |
User Interface, Alerts & Controls
| Front Panel LCD Display | Digital display reports total PDU output current in amps |
|---|---|
| Front Panel LEDs | 8 LEDs display power on-off status for each C13 output receptacle, plus 2 additional LEDs to indicate input power status for primary and secondary inputs |
| Switches | Toggle switch near digital display enables the setting of "HI" for 220, 230 or 240V nominal applications or "LO" for 200 or 208V applications |
Physical
| Form Factors Supported | 1U rackmount |
|---|---|
| Material of Construction | Metal |
Environmental
| Operating Temperature Range | 0C ~ 40C (32F ~ 104F) |
|---|---|
| Storage Temperature Range | -30°C to +50°C (-22°F to +122°F) |
| Relative Humidity | 5-95% (non-condensing) |
Communications
| SNMP Compatibility | Pre-installed LX platform interface provides remote monitoring via Java-free HTML5 web interface, telnet, SSH and SNMP management systems |
|---|
Standards & Compliance
| Certifications | Tested to UL 60950 (USA, Canada), CE (Europe), Class A (Emissions), NOM (Mexico), RoHS Complaint, TAA Compliant |
|---|
Warranty
| Product Warranty Period (Worldwide) | 2-year limited warranty |
|---|
Documents and Downloads
Documents and Downloads
- Owner's Manual for Switched/Metered Rack PDU with ATS 933721 (Multi-Language)
- Owner's Manual for Switched/Metered Rack PDU with Automatic Transfer Switch (Multi-language)
- Owner's Manual for WEBCARDLX (English)
- Single Phase Power Distribution Units (PDUs) Visio Stencil
- Single-Phase Power Distribution Units (PDUs) Stencil Preview
- 120V Power Distribution Unit (PDU) Models and Specifications List (English)
- 230V Power Distribution Unit (PDU) Specification Brochure (English)
- 120V Power Distribution Unit (PDU) Brochure (English)
- 230V Power Distribution Unit (PDU) Brochure (English)
- Integrated Solutions Brochure (English)
- Auto Probe Solution for Monitoring and Rebooting Locked-Up Devices (English)
- Storm Season is Here Again Flyer (English)
- EC Declaration
- PDU Buying Guide
- PDU Installation Options
- Custom Products from Tripp Lite Are One Call Away
- Outlet Plug Types
- 7 Steps to Choosing the Right Single-Phase or 3-Phase PDU
- PDU Types
Payment & Security