Plenum or riser? Indoor or outdoor? Armored or unarmored? Work through these four checks before choosing your cable. Fire rating, environmental suitability and mechanical protection are separate requirements: one does not replace the others.

1. Where will the cable run?

  • Indoors, in a dry protected route: Select the fire rating appropriate to the actual pathway and project specifications.
  • Outdoors, exposed to sun or weather: Check the exact cable datasheet for outdoor use, sunlight resistance, moisture suitability and operating temperature. An indoor CMP or CMR marking alone does not establish outdoor suitability.
  • Underground in conduit: Check for suitability for wet locations and underground conduit. Do not assume conduit keeps cable dry.
  • Directly in soil: Choose a cable explicitly identified by its manufacturer as suitable for direct burial. An outdoor label alone is not enough.
  • Both indoors and outdoors: Look for a cable with the appropriate indoor/outdoor ratings, or have the designer specify the transition at the building entrance.

2. Plenum or riser?

  • CMP, plenum: A communications-cable fire rating addressing flame spread and smoke production, used for plenum applications. Have the designer confirm whether the pathway is an environmental-air space. Do not classify it from the presence of a dropped ceiling alone.
  • CMR, riser: A communications-cable fire rating addressing flame spread in vertical riser applications. Do not select CMR as a substitute where CMP is specified.

Check the cable family: CMP and CMR are communications-cable designations, not universal labels for every cable. Fiber, fire-alarm and other cable types can use different listing designations. Match the exact product listing to the application.

3. “Can I use riser cable in buried conduit?”

Not on the strength of its CMR marking alone. Verify that the exact product is also suitable for wet locations and the planned underground pathway. Likewise, plenum-rated does not automatically mean outdoor-rated or direct-burial-rated. Check all applicable markings and the manufacturer's installation instructions.

4. Armored or unarmored?

  • Armored: Consider when the route calls for additional mechanical protection. Check the product's stated crush, impact and other protection characteristics. Armor alone does not establish outdoor, wet-location or direct-burial suitability.
  • Unarmored: Consider for protected pathways where the cable and pathway together meet the project's mechanical-protection requirements.
  • Metallic or dielectric armor: Have the installer check bonding and grounding requirements for metallic components. Dielectric armor options exist; verify the exact construction rather than assuming every armored cable contains metal.

Before you order

Confirm the complete route, required cable-family listing, indoor/outdoor and moisture ratings, burial method, mechanical protection, and any building-entry transition or bonding requirements. Then verify the exact part number's datasheet and jacket markings.

Confirm local requirements: This is a general product-selection aid, not legal advice, a code interpretation or approval of an installation. Ask your project designer, qualified installer and local authority having jurisdiction to confirm the applicable code edition, local requirements and project specifications before purchase or installation.

Technical references