Description
Description
Maximal1RHD rack mount access power controller distributes and switches power to access control systems and accessories. It converts a 115VAC 50/60Hz input into eight (8) independently controlled 12VDC or 24VDC PTC protected outputs. Outputs are activated by an normally open (NO) or normally closed (NC) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. This unit will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the outputs.
Specifications
Specifications
Enclosure
- Modular 2U standard EIA 19" rack mount chassis.
- Dimensions 19.12"W x 3.25"H x 8.5"D (486 mm W x 83 mm H x 216 mm D).
- Allow 1/2U space on top and bottom of the unit for ventilation.
Input
- 115VAC 60Hz., 1.9A.
- Normally closed [NC] or normally open [NO] dry contact inputs (switch selectable).
Outputs
- 12VDC @ 4A or 24VDC @ 3A total output current.
- Eight (8) PTC protected outputs (auto-resettable).
- Maximum current per ACM8R-M output is 2A.
- Individually selectable Mag Lock/Strike (Fail-Safe, Fail-Secure) solid state fuse protected outputs.
- Thermal and short circuit protection with auto reset.
Fire Alarm Interface
- Latching or Non-Latching fire alarm reset switch individually selectable for each output.
- Remote reset capability for latching Fire Alarm Interface mode
- Fire Alarm disconnect input options:
- a) Normally open [NO] or normally closed [NC] dry contact input.
- b) Polarity reversal input from FACP signaling circuit.
Visual Indicators
- Individual Output Status LEDs located on the front panel.
Battery Backup
- Built-in charger for sealed lead acid or gel type batteries (if batteries are required install separate enclosure).
- Automatic switch over to stand-by battery when AC fails.
- Zero voltage drop when unit switches over to battery backup (AC failure condition).
Weights (approximate)
| Product Weight | 10.7 Lbs. (4.85 kg). |
|---|---|
| Shipping Weight | 12.7 Lbs. (5.76 kg). |
Documents and Downloads
Documents and Downloads
- Altronix MAXIMAL1RHD Data Sheet
- Altronix MAXIMAL1RHD Data Sheet
- Altronix MAXIMAL1RHD Fichas Tecnicas
- Altronix MAXIMAL1RHD Installation Instructions
- Altronix MAXIMAL1RHD Altronix_MAXIMAL1RHD_Power_Controller_Installation_Instructions_prior_to_Feb._9,_2015.pdf
- Altronix MAXIMAL1RHDGuia de Instalacion
- Altronix MAXIMAL1RHD Lifetime Warranty
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.