Description
Description
The suggested sound pressure level for each notification zone used with alarm notification appliances is at least 15 dB above the average ambient sound level, or 5 dB above the maximum sound level having a duration of at least 60 seconds, whichever is greater, measured 5 feet (1.5 m) above the floor. The average ambient sound level is A-weighted (fast response) sound pressure measured over a 24-hour period.
Doubling the distance from the notification appliance to the ear will theoretically result in a 6 dB reduction of the received sound pressure level. The actual effect depends on the acoustic properties of materials in the space. A 3 dBA difference represents a barely noticeable change in volume.
KIDDE is a registered trademark of Kidde IP Holdings Limited and is in no way affiliated with All Data Resource
Main Features
- Outdoor and indoor rated
- Low-profile design
- Wall or ceiling mount
- Room-side wiring accepts 18 to 12 AWG (0.75 to 2.5 mm2)
- Wide operating temperature range
- Field-selectable settings
- Fully-compatible with Genesis synchronization protocols
- Standard and high-output strobe intensities
- Horn only and horn-strobe options
Specifications
Specifications
Specifications
| UPC Code | 793016039880 |
|---|---|
| Product Model | WG4WF-SVMHC |
| Brand Name | Kidde Commercial |
| Country of origin | China. Country of origin is subject to change. |
| Device Type | HORN / STROBE |
| UNSPSC Code | 46171600 |
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.