Description
Description
The addressable Isolator Base 6” (paD100-IB) comes with an integrated isolator module included. The base has a locking feature for the sensor that may be used or removed in the field. Once the head is removed, the isolator is accessible in the bottom of the unit.
The isolator will open the Signaling Line Circuit down stream when a short circuit is detected. This will provide devices between the control panel and the isolator to continue to operate. The short is indicated by a steady red LeD and once the short is removed the unit will return to normal operation.
Potter Electric Signal - PAD-100-IB - Features
- Isolator integrated into base
- Self restoring
- Red LED indication of short circuit
- Terminals accept 22 to 12 aWg wire sizes
- Supports Class a, Class X and Class B wiring
- Does not require SLC Loop address
- UUKL Listed for Smoke Control
Specifications
Specifications
Potter Electric Signal - PAD-100-IB - Specifications
| Working Range for SLC | 24 VDC |
|---|---|
| active indicator | 1 LED (red) |
| applicable SLC wiring style | Class a, B and X |
| Maximum number of paD100-IB per SLC Loop | 127 |
| Installation temperature range | 32°F to 120°F (0°C to 49°C) |
| Operating relative humidity range | 0% to 93% (Non-condensing) |
| Color | eggshell White |
| Height | 0.75 in (19mm) |
| Diameter: | 6.3 in (166 mm) |