Description
On-line double-conversion UPS provides pure sine wave AC output to server and network equipment in data centers and computer rooms.
Features
- Double-Conversion UPS Protects Equipment against Damage, Downtime and Data Loss
- This 200/208/220/230/240V 50/60 Hz UPS system maintains perfect output by converting AC input to DC, then reconverting UPS output to fully regulated sine wave AC with +/-2% voltage regulation in online and battery modes. Featuring a 2700W capacity, high 0.9 power factor, 570 joules of surge suppression, true on-line operation with pure sine wave output and zero transfer time to battery mode in on-line double-conversion mode, the SmartOnline SUINT3000LCD2U double-conversion UPS provides the highest level of AC power protection and battery backup for critical network closet, computer room and data center equipment.
- Set Power Strategies to Reflect Your Protection Priorities
- Pick your power strategy, from precise power for sensitive systems to the highest possible electrical efficiency, while ensuring 100% uptime. Choose from five selectable strategies: Max Efficiency, Max Quality, Frequency Regulation, Frequency Conversion and Auto Adaptive, which automatically offers increased efficiency when power conditions are good and enhanced power quality when power conditions are poor.
- Individually Controllable Load Banks Let You Access and Control Outlets Remotely
- Six C13 and two C19 outlets are split evenly into two switchable load banks, allowing you to reboot select components or shed loads remotely. In addition to those eight outlets, this UPS provides two more C13 outlets in their own unswitched bank for powering critical components.
- Reliable, Expandable Battery Backup Keeps You Operational Through Power Outages
- The field-replaceable, hot-swappable internal battery (RBC72S) provides 13.5 minutes of support at half load (1350W) and five minutes at full load (2700W), keeping protected equipment operational through power failures. For mission-critical applications demanding scalable extended runtime, the UPS supports “smart” external battery packs, such as Tripp Lite’s BP72V18-2US (sold separately). Both the internal and external batteries are automatically sensed and configured during replacement to offer accurate runtime-remaining and battery age notifications during outages. The intelligent battery management system with temperature-compensated charging extends battery life.
- Automatic Bypass Maintains Utility Output During Fault Conditions
- Auto-bypass mode keeps connected equipment powered and operational, even during UPS fault conditions.
- ENERGY STAR-Certified Economy Mode Helps You Save Money and Protect the Environment
- By meeting strict EPA efficiency guidelines, this ENERGY STAR-certified UPS system helps you save money and energy. A power-saving Economy mode setting option offers enhanced efficiency and reduced BTU output when utility power is already high quality.
- Automatically Turns Back On After Power Is Restored
- Battery-independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement.
- Intuitive Front-Panel Interface for Convenient UPS Operation and Monitoring
- The front-panel LCD screen reports UPS operating mode, detailed UPS status and site-power information, as well as a variety of advanced UPS setup and configuration options. LEDs indicate AC input/output, battery and fault status.
- Advanced Communications Ports Allow for Automatic Saves and Shutdowns
- RS-232 and HID-compliant USB ports connect to a computer running Tripp Lite’s free downloadable PowerAlert software to enable safe unattended file saves and system shutdown in case of a prolonged power failure. An EPO port connects the UPS to a contact closure switch to enable emergency inverter shutdown. Cables are included.
- Optional WEBCARDLX Network Interface Offers 24/7 Access
- The optional WEBCARDLX (sold separately) with the latest version of PowerAlert Device Manager firmware (PADM20) provides enhanced remote management capabilities, including customizable dashboard graphs to fit user preferences. The PADM20 upgrade and Tripp Lite’s PowerAlert Element Manager (PAEM) software form a powerful tool for expanding maintenance functions in large installations, including firmware update checks and backup and restoration of device configurations. Auto Probe allows a UPS with switched loads to automatically reboot devices if a network communication failure is detected. This preserves uptime and minimizes the time and expense associated with on-site support.
- Versatile Installation Options
- Hardware is included for mounting the UPS system in 2U of space in an EIA-standard 19-inch 4-post rack. Use the optional 2POSTRMKITWM (sold separately) for 2-post rack mounting or the optional 2-9USTAND (sold separately) for mounting in an upright tower position. The C20 power inlet accepts a variety of user-supplied input cords.
Specifications
Specifications
Overview
| UPC Code | 37332185631 |
|---|---|
| UPS Type | On-Line |
Input
| Rated input current (Maximum Load) | 14.97A |
|---|---|
| Nominal Input Voltage(s) Supported | 200V AC; 208V AC; 220V AC; 230V AC; 240V AC |
| UPS Input Connection Type | C20 inlet |
| Input Phase | Single-Phase |
Output
| Output Volt Amp Capacity (VA) | 3000 |
|---|---|
| Output kVA Capacity (kVA) | 3 |
| Output Watt Capacity (Watts) | 2700 |
| Output kW Capacity (kW) | 2.7 |
| Output Capacity Details | DE-RATING INFORMATION: Max output in Frequency Conversion mode is reduced to 1890 watts for 208/220/230/240V output voltages; Max output is reduced to 2160W at 200V output voltage in all operating modes OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for 30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits). |
| Power Factor | 0.9 |
| Crest Factor | 03:01:00 |
| Nominal Voltage Details | Nominal output voltage is user configured on first power-on |
| Frequency Compatibility | 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion |
| Frequency Compatibility Details | Output frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion operation |
Battery
| Battery Type | Valve Regulated Lead Acid (VRLA) |
|---|---|
| Full Load Runtime (min.) | 5 min. (2700w) |
| Half Load Runtime (min.) | 13.5 min. (1350w) |
| Expandable Battery Runtime | Supports extended runtime with optional external battery packs |
| Expandable Runtime | Yes |
Voltage Regulation
| Voltage Regulation Description | Online, double-conversion power conditioning |
|---|---|
| Overvoltage Correction | 2% output voltage regulation during overvoltages to 288 |
User Interface, Alerts & Controls
| Front Panel LCD Display | Interactive front-panel LCD interface reports UPS operating mode, detailed UPS status and site-power information; LCD interface also enables a variety of advanced UPS setup and configuration options |
|---|---|
| Switches | 5 front panel switches: On/Off, Up, Down and Escape |
| Alarm Cancel Operation | Power-fail alarm can be silenced by following on-screen prompts |
Surge / Noise Suppression
| UPS Dataline Suppression Details | Single line dialup / network dataline protection included |
|---|---|
| EMI / RFI AC Noise Suppression | Yes |
| AC Suppression Joule Rating | 570 |
| AC Suppression Response Time | Instantaneous |
Communications
| Network Management Cards | SNMPWEBCARD ; WEBCARDLX |
|---|---|
| PowerAlert Software | For local monitoring via the UPS’s built-in communication ports; download PowerAlert Local software at https://www.tripplite.com/poweralert |
| Communications Cable | USB and DB9 cabling included |
| WatchDog Compatibility | Supports Watchdog application; OS and hard-reboot restart options for remote applications |
| Communications Interface | Contact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |
Documents and Downloads
Documents and Downloads
- SUINT3000LCD2U runtime chart
- Owner's Manual for Single-Phase Rackmount On-line UPS with Built-in LCD (Multi-language)
- PowerAlert Device Manager (PADM) 20.0.0 Command Line Interface User's Guide (English)
- Single-Phase UPS Systems Visio Stencil
- Single-Phase UPS Systems Visio Stencil Preview
- Operating Systems Remotely Flyer (English)
- EC Declaration 1 SU3000LCD2UHV 2 SUINT3000LCD2U
- PADM20 High-Level Overview